The black-labelled CO2 extinguisher is the standard answer for fires involving live electrical equipment in UK premises. It is also rated for Class B fires (flammable liquids), it leaves no residue, and it is by some way the most common second extinguisher you will see paired with a water or foam unit on a typical office wall.
This page covers what a CO2 extinguisher actually does, where it belongs, the cautions that genuinely matter (the cold horn, confined spaces, the limits on Class A), and one detail that catches a lot of premises out: CO2 has a ten-year overhaul interval while still needing routine checks and annual basic servicing.
What a CO2 fire extinguisher is
A CO2 extinguisher is a high-pressure cylinder containing carbon dioxide stored as a liquid. The body is signal red with a black panel near the label — the black panel is the visual identifier. There is no separate charge propellant; the CO2 itself is both the agent and the propellant, which is why the cylinder is built to a higher pressure rating than water or foam.
The discharge horn is distinctive — a wide, flared plastic cone (sometimes wrapped in insulating material) at the end of a short rubberised tube. When the extinguisher is operated, liquid CO2 flashes to gas as it expands through the horn, dropping the temperature dramatically along the way.
UK CO2 extinguishers are tested under BS EN 3 and selected and positioned under BS 5306-8:2023, the same framework as the other types. Standard UK capacities are 2 kg and 5 kg.
How CO2 extinguishers work
CO2 extinguishes by displacing the oxygen around the fire. As the liquid CO2 expands to gas, it produces a large volume of cold, dense gas that flows over and around the fuel surface, pushing breathable air out of the way. With oxygen levels dropping below the threshold needed to sustain combustion, the fire goes out.
A small secondary effect comes from the cooling: the rapid expansion of compressed CO2 absorbs heat, which is why the discharge horn becomes so cold in use. The cooling helps slightly, but the dominant mechanism is oxygen displacement.
Two practical implications follow.
The agent doesn't cool the burning material much
Once the gas disperses (which it does quickly, especially outdoors or in any room with normal ventilation), the fuel is still hot. If there is a continuing source of heat — a shorted wire, a smouldering plastic — the fire can re-ignite. CO2 is excellent at putting fires out; it is less excellent at keeping them out.
The agent leaves no residue
This is the property that matters most for electrical and electronic equipment. Discharge a powder extinguisher onto a server rack and the residue may seriously damage the equipment. Discharge a CO2 extinguisher and the rack is functionally clean.
What CO2 extinguishers tackle
Class B and live electrical equipment. The standard examples:
- Class B: small, contained flammable-liquid fires — a tray of solvent, a bench-top fuel spill, a small fire in a fume cupboard.
- Live electrical equipment: the dominant use case. Servers, IT cabinets, photocopiers, electrical risers, distribution boards (with appropriate caution — see below), kitchen appliances, anything energised that has caught fire.
CO2 is non-conductive, which is the whole reason it is the standard for electrical fires. The agent will not create a path for current back to the user. BS 5306-8:2023 (clause 7.7.1) names CO2 explicitly as one of three permissible non-conductive media for use on live electrical equipment, alongside non-conductive powder and clean agents.
What CO2 doesn't tackle:
- Class A (solids — paper, wood, fabric). CO2 will knock the visible flames down but won't cool the material, and re-ignition is highly likely. CO2 is not a Class A answer.
- Class F (cooking oils). The high-pressure discharge can splash burning oil out of the pan, and the gas does not interact usefully with the oil chemistry. Wet chemical, fire blanket, or water mist is the right answer. See our cooking oil fire guide.
- Class C (flammable gases). CO2 may temporarily knock the fire down, but the gas leak is the underlying problem; isolation of the supply is the only real fix.
The cold horn — why it matters
CO2 discharge can make the horn and exposed parts dangerously cold, with a risk of cold burns. Hold only the manufacturer-designated handle or insulated grip. Do not grip an unprotected horn, pipe or other cold part.
Grip arrangements differ by model. Follow the instructions on the unit and the handling technique covered in training; a frost-resistant horn is not permission to hold any part of it.
The cold also has a secondary effect at the fire. The first second or two of discharge produces a forceful, audible blast of gas at high velocity — enough to scatter loose paper, light objects or burning embers around the room. Aim with that in mind, particularly in office or document-storage settings.
Confined spaces — the genuinely serious caution
CO2 can create a dangerous atmosphere, particularly in enclosed or poorly ventilated spaces. It is colourless and odourless; high concentrations are hazardous as well as displacing oxygen. Normal room ventilation should not be assumed to make discharge or re-entry safe.
A confined space is substantially enclosed and has a reasonably foreseeable specified risk, such as serious injury from fire or explosion, loss of consciousness, asphyxiation or drowning. Size alone does not determine whether the legal definition applies.
BS 5306-8:2023 specifically cautions against the use of both CO2 and dry powder extinguishers in confined spaces unless the risk has been mitigated through a health and safety risk assessment. In practice, that means CO2 belongs in offices, retail spaces, and ordinary indoor environments with normal ventilation; for genuinely confined spaces, fire suppression is more often handled through fixed systems or through evacuation and fire-and-rescue response than through portable extinguishers.
After any fire or significant CO2 discharge, leave the area and prevent re-entry until it is assessed as safe. Do not go back into a potentially dangerous atmosphere to open windows; ventilation and clearance should be managed safely by competent responders.
What about Class A — re-ignition risk
CO2 will visibly knock down a small Class A fire. The flames go out; the immediate danger appears to pass. But because the agent does not cool the fuel, the underlying material remains at or near its ignition temperature. As soon as the gas disperses (which can be within seconds), oxygen reaches the still-hot fuel and the fire re-ignites.
The practical consequence is that a CO2 unit without a Class A rating should not be relied on for Class A cover. A typical workplace pattern is to place a CO2 extinguisher near electrical risk and pair it with a Class A unit (water or foam) at the same fire point. The CO2 deals with the electrical problem; the water or foam deals with the burning paperwork that probably accompanies it.
This is why BS 5306-8 indicates that CO2 should generally be provided alongside a water or foam extinguisher in offices and commercial premises, rather than as a sole provision.
The 10-year overhaul
This is the operational detail that catches a lot of premises out. Under BS 5306-3:2017, water, foam, dry powder and wet chemical extinguishers all undergo an extended service every 5 years. CO2 extinguishers do not. CO2 cylinders are subject to a ten-year overhaul under the conventional maintenance schedule, reflecting the higher cylinder pressure rating and the very different internal conditions.
What that means in practice: a CO2 extinguisher you bought today will receive an annual basic service for nine years, then an overhaul (which includes hydraulic pressure testing of the cylinder) at the ten-year mark. Many premises run their CO2 units to the 10-year point and then replace rather than overhaul, because replacement is often cheaper than the cost of overhaul plus discharge testing.
The mismatch with the 5-year cycle for the rest of the cluster is the easiest schedule mistake to make. If your servicing contract treats every unit on a 5-year extended-service cycle, your CO2 units are over-serviced at year 5 and under-budgeted at year 10. Confirm with your contractor that the schedule matches the unit type. The full picture is on our fire extinguisher servicing and inspection page.
Where CO2 extinguishers belong
Typical UK placements:
Offices and retail
A 2 kg or 5 kg CO2 unit at each fire point, paired with a water or foam unit. The CO2 covers electrical risk (printers, screens, kitchens with electric appliances, server cabinets); the water or foam covers Class A.
Server rooms and IT cabinets
A CO2 unit within a few metres, mounted at standard height, with clear signage. The residue-free property is the whole point — powder residue can cause additional damage and difficult cleaning.
Electrical risers and distribution rooms
CO2 is the standard, often as the only portable extinguisher in the immediate vicinity. Be cautious about confined-space asphyxiation risk in small rooms; ventilation matters.
Commercial kitchens (back-of-house electrical)
CO2 for refrigeration, electric ovens, dishwashers — paired with wet chemical and a fire blanket on the cooking line.
Workshops and laboratories
CO2 alongside dry powder or foam for Class B contained liquid fires, particularly where small quantities of solvents are used near electrical bench equipment.
CO2 is less common in domestic settings — the cylinders are heavier, the use case is narrower, and a water mist extinguisher is often a more practical single-unit answer. Where CO2 is used at home, it is usually for a specific reason (a home server, a workshop in a garage, a hobbyist setup with electrical equipment).
How to use a CO2 extinguisher
The PASS technique applies — Pull, Aim, Squeeze, Sweep — with three CO2-specific notes:
- Hold the extinguisher by the body and the operating lever, never by the discharge horn.
- Use the manufacturer’s operating distance and the technique covered in training. Keep a clear escape route, and do not move into heat or smoke to make the discharge reach.
- Aim at the base of the fire and sweep across the burning material. The first second of discharge is the most forceful; expect a noisy, visible blast.
For a Class B liquid fire, follow the particular CO2 unit’s instructions and your training. CO2 does not form a lasting blanket or provide reliable cooling, so re-ignition remains possible after the gas disperses. Withdraw if the fire is not immediately controlled or safe escape is threatened.
For the full step-by-step, see our PASS technique guide.
Frequently asked questions
Can a CO2 extinguisher be used in a server room?
CO2 may be selected for electrical risks, but a small or enclosed server room creates additional gas-exposure risks. Equipment, location and emergency procedures must follow a competent assessment. Do not enter a hazardous atmosphere to fight a fire or ventilate the room.
Why doesn't CO2 work on Class A fires?
CO2 puts the visible fire out by displacing oxygen, but it doesn't cool the fuel. As soon as the gas disperses, the still-hot Class A material re-ignites. CO2 is good for electrical and small Class B fires; for Class A, water or foam is the right choice.
What's the asphyxiation risk?
CO2 can create a hazardous atmosphere through high concentration and oxygen displacement. Avoid use in confined spaces and do not assume ordinary ventilation makes it safe. Leave after an incident and await competent clearance before re-entry.
Why is the discharge horn dangerous?
The horn becomes extremely cold during use because the rapid expansion of compressed CO2 absorbs heat. Direct skin contact with the horn produces a frostbite injury within seconds. Hold the extinguisher by the handle and lever, never by the horn.
Why do CO2 extinguishers need overhaul at 10 years rather than 5?
The cylinder pressure rating and internal conditions differ from water-based extinguishers, and the BS 5306-3:2017 maintenance schedule reflects that. Water, foam, dry powder and wet chemical extinguishers are on a 5-year extended-service cycle; CO2 is on a 10-year overhaul cycle.
What size CO2 extinguisher do I need?
Choose capacity and location from the assessed electrical and fire risks, room conditions and applicable selection guidance. A general statement that 2 kg is sufficient cannot replace that assessment.
Where this connects
For the wider question of which extinguisher to use on an electrical fire — when to choose CO2 versus dry powder versus tested water mist — see our guide to fire extinguishers for electrical fires. For the dry powder alternative, see our dry powder fire extinguisher page. For where CO2 sits in the wider type and colour system, the fire extinguisher types hub is the place to start.
If you are responsible for setting up a workplace's fire safety from scratch — including who needs to be trained — the online fire safety awareness training course covers the basics every UK employee needs.
Related guides
- Who Is Responsible for Fire Extinguishers in the UK?
- Fire Extinguisher Disposal: The UK Guide
- Fire Extinguisher Servicing and Inspection: The UK Guide
Sources & references
Official guidance and standards checked on 15 October 2026.
- Government — CO2 selection and limitations
- BAFE — CO2 annual service and overhaul
- HSE — confined spaces and hazardous atmospheres
- BS 5306-8:2023
- BS 5306-3:2017