Britain has settled on five primary types of fire extinguisher, each designed for a specific kind of fire. The right one tackles the flames; the wrong one can make things worse, sometimes dangerously so. This guide walks through what each of the five types does, what the colours mean, which fires they handle, and where the regulations sit in 2026.

A note before we begin. UK fire safety law does not name a brand or model you must buy. What it requires is that the equipment in your premises matches the risks identified in your fire risk assessment, and that it is maintained in working order. Everything below is the framework for making those judgements well.

The UK colour code at a glance

Modern UK fire extinguishers have a red body — specifically “signal red” — with a smaller coloured panel near the label that tells you what is inside. The red body makes the unit visible in smoke; the coloured panel tells you what kind of fire it tackles. The system is set out in BS EN 3 (the European product standard) and BS 5306-10:2019 (the colour-coding standard).

The five panels you will see in UK premises:

Colour panelTypeMain fire classes
Red (no contrast panel)WaterA
CreamFoamA and B
BlueDry powderA, B, C; electrical use only as marked
BlackCarbon dioxide (CO2)B and electrical
YellowWet chemicalF; additional A/B ratings vary

Older extinguishers from before 1997 had bodies coloured throughout — a fully blue powder unit, a fully cream foam unit, and so on. Those remain legal in most premises covered by the Regulatory Reform (Fire Safety) Order 2005, provided they are not defective and are still being maintained. New replacements all follow the red-body-with-coloured-panel convention.

The five primary extinguisher types

Each section below is a quick orientation. Each links to a fuller page with the chemistry, capacities, sizing, and the situations each one belongs in.

Water (red label)

The traditional, simplest extinguisher. Water tackles Class A only — solid combustibles like paper, wood, fabric and most plastics. It cools the burning material below its ignition temperature, leaves no chemical residue, and is by far the cheapest type to buy and to service.

Do not use an ordinary water jet on flammable liquids or live electrical equipment: it can spread burning fuel or create an electric-shock hazard. Water-mist and additive products have different tested capabilities; use only the fire classes and electrical limits on the particular unit. See our water extinguisher guide.

Foam (cream label)

Foam extinguishers handle Classes A and B — solids and flammable liquids. The agent forms a film over a burning liquid, cutting off vapour and oxygen while cooling the fuel. They are a common workplace choice because most premises carry both Class A risks (paper, furniture) and small Class B risks (cleaning solvents, paint, fuel for forklifts).

Foam formulation affects compliance. Specific PFOA foam exemptions ended on 4 July 2025, with use prohibited from 5 July under the UK POPs regime. HSE’s consultation on wider Great Britain PFAS foam restrictions closed in February 2026; that proposal is separate from existing restrictions. Check the product’s documented composition, rather than assuming all AFFF is banned or all C6 is compliant. See our foam extinguisher guide.

Carbon dioxide (black label)

CO2 extinguishers handle Class B and live electrical equipment fires. The gas displaces oxygen around the fire and leaves no residue, which is why CO2 is the standard choice for offices, server rooms, and electrical cabinets. Two cautions matter. The discharge horn becomes very cold during use — frostbite is a real risk if you grip it directly. And CO2 must not be used in confined spaces because it can asphyxiate the user.

CO2 still needs routine checks and annual basic servicing. Its standard overhaul interval is ten years; that differs from the five-year extended service for conventional water-based and powder units. See our CO2 guide.

Dry powder (blue label)

ABC dry powder is rated for Class A, B and C fires. Electrical suitability depends on the product’s own marking and operating conditions. The powder interrupts the combustion reaction; its discharge also creates visibility and breathing hazards.

Versatility comes with trade-offs. Powder discharge clouds the air, drastically reducing visibility, and inhalation is a respiratory hazard. BS 5306-8:2023 (clause 5.4.3) specifies that powder extinguishers should generally not be specified for indoor use unless mitigated by a health and safety risk assessment. They are at their best in garages, forecourts, vehicles, workshops, and other open or outdoor environments.

Specialist Class D variants exist for combustible-metal fires: L2 powder for lithium metal, M28 powder for magnesium, sodium, potassium and others. L2 powder is not the answer to lithium-ion battery fires — that is a different problem under the new Class L classification, covered below. The full guide is our page on dry powder fire extinguishers.

Wet chemical (yellow label)

The yellow-labelled wet chemical extinguisher is designed for Class F — cooking oils and fats. The agent (usually a potassium acetate solution) sprays as a fine mist that reacts with burning oil through a process called saponification, forming an inert soapy foam layer that smothers the flames and prevents re-ignition.

Wet chemical is a common choice for assessed commercial cooking-oil hazards. Some products also carry A or B ratings; check the particular label. At home, prioritise safe cooking, alarms and escape, and follow fire-service advice to leave a burning pan and call 999. See our guide to wet chemical fire extinguishers.

A modern sixth option: water mist

This guide groups five common agents, with water mist as another product option. Mist systems differ in water quality, nozzle design and tested fire ratings. Use only the classes and electrical conditions explicitly permitted by the particular unit’s instructions.

Water mist is not a universal replacement for other equipment. Assess its tested capacity and suitability for the actual fire risks, particularly deep-fat cooking and electrical equipment, with a competent supplier.

Which extinguisher for which fire — quick reference

A working table for everyday selection. Always confirm specifics against the extinguisher’s own label and your fire risk assessment.

Fire scenarioRecommendedAcceptable alternativeDo NOT use
Class A — solids (paper, wood, fabric)WaterFoam, water mist, ABC powder, wet chemical (small)CO2
Class B — flammable liquids (petrol, paint)FoamCO2 (small contained), ABC powder (outdoor)Ordinary water jet; products without the relevant B rating
Class C — flammable gasesLeave and call 999; isolation by someone competent only if safe—Water, foam, CO2
Class D — combustible metalsL2 or M28 specialist powder—Water, foam, CO2, ABC powder
Class F — cooking oilsWet chemicalFire blanket (small), water mist with F-ratingWater, foam, CO2, ABC powder
Live electrical equipmentCO2Other agents only within their marked electrical-use limitsWater, standard foam
Lithium-ion battery (Class L)Specialist suppression, evacuateOnly equipment supported by relevant battery-specific test evidenceDo not infer battery suitability from ordinary fire-class ratings

For deeper “which extinguisher and why” answers on the trickiest scenarios, see the right extinguisher for an electrical fire, the right extinguisher for a chip-pan or kitchen oil fire, and the right extinguisher for petrol or other flammable liquids.

The five UK fire classes — a brief tour

Fires are classified under BS EN 2 by the type of fuel involved. There are five UK fire classes: A, B, C, D and F. (You may notice E is missing from that list — that is on purpose; we will get to it.)

  • Class A — solid combustibles. Wood, paper, textiles, soft plastics, most household materials.
  • Class B — flammable liquids. Petrol, diesel, kerosene, paint, solvents, alcohols.
  • Class C — flammable gases. Propane, butane, methane, LPG.
  • Class D — combustible metals. Lithium, magnesium, sodium, potassium, aluminium swarf.
  • Class F — cooking oils and fats. Animal and vegetable fats; the chip-pan fire.

For the deeper version, including examples by class and the right extinguisher choices, see our guide to UK fire classes.

Halon and other decommissioned types

Some older premises still have green-bodied halon extinguishers tucked in a cupboard. These were banned for general use in the UK in 2003 under the Montreal Protocol because halon depletes the ozone layer. If you find one, do not use it and do not put it in general waste — halon disposal must go through a specialist or the original manufacturer. We cover the right route on our extinguisher disposal page.

A note on the older all-coloured-body extinguishers from before the 1997 standardisation: those remain legal in most UK premises covered by the Fire Safety Order, provided they are still being maintained and are not defective. You do not need to replace them on colour grounds alone. New units carry red bodies with coloured panels.

What’s new in 2026: BS ISO 3941 and Class L

January 2026 brought the most significant fire-classification update in many years. BS ISO 3941:2026 introduced Class L — a dedicated category for fires involving lithium-ion battery cells and packs.

Lithium-ion battery fires behave differently from anything else in the standard list. They generate heat through a self-sustaining electrochemical reaction inside the cell (“thermal runaway”); they release oxygen as part of that reaction, which means smothering doesn’t work well; they re-ignite easily, sometimes hours after they appear to be out; and they emit toxic gases. That hazard profile is poorly served by the existing Class A, Class B or “live electrical equipment” frameworks.

Class L in BS ISO 3941:2026 identifies lithium-ion battery fires. A classification does not establish that a product is effective on a particular battery. Check independently verified test evidence and the limits of any claimed battery-fire rating; do not infer suitability from an ordinary A, B or F rating.

Fire risk assessments should address the actual battery hazards, including charging, storage, escape routes and emergency arrangements. The new classification helps describe the hazard but does not itself create a separate statutory requirement to use the term “Class L”.

Common things people read online that aren’t quite right

Several mistakes circulate widely enough to be worth correcting in one place.

There is no Class E fire in the UK

Many older guides still list “Class E” for electrical fires. Under BS EN 2, electricity is an ignition source or a hazard, not a fire class — electricity itself doesn’t burn, it just causes other things to. Modern UK extinguishers carry markings to indicate suitability for use on live electrical equipment, but they don’t have a “Class E” rating because the class doesn’t exist.

Distinguish BS EN 2 from the newer Class L classification

You will sometimes see lists with Class A, B, C, D, E and F. The error usually comes from including the historical “Class E” or counting water mist as a class rather than an extinguisher type. The five UK classes under BS EN 2 are A, B, C, D and F. Class L from BS ISO 3941:2026 is the genuine new entry.

The law does not require “two extinguishers per floor” of any particular type

What the Regulatory Reform (Fire Safety) Order 2005 requires is appropriate firefighting equipment based on the findings of your fire risk assessment. BS 5306-8:2023 provides selection and positioning guidance — coverage, travel distances and rating combinations — but does not impose a one-size-fits-all rule.

CE marking has not been replaced by UKCA

As of writing, both marks remain valid in Great Britain for fire extinguishers; the deadline for ending CE acceptance has been deferred. Northern Ireland uses CE, with UKNI added where the applicable UK-body assessment route requires it under the Windsor Framework. A UK-supplied extinguisher displaying CE alone is not non-compliant.

Annual servicing is not strictly the law — but it is the recognised standard

The Fire Safety Order requires suitable maintenance. The recognised conventional schedule is at least monthly visual checks, annual basic servicing, five-year extended service for most water-based and powder units, and ten-year CO2 overhaul. Follow the relevant manufacturer instructions and competent maintenance advice. BAFE SP101 is a third-party certification route. See our servicing guide.

Frequently asked questions

How many types of fire extinguisher are there in the UK?

Five primary types — water, foam, CO2, dry powder and wet chemical — each with a distinct coloured panel. Water mist is increasingly common as a sixth option and is recognised under BS EN 3, although it is not a separate fire class.

Do older all-coloured-body extinguishers (pre-1997) need to be replaced?

No, not on colour grounds alone. They remain legal in most premises covered by the Fire Safety Order, provided they are still being serviced and are not defective. They get replaced at end of life like any other extinguisher.

Is “signal red” a real specification?

Yes. Modern UK fire extinguisher bodies are coloured signal red (RAL 3000), specified under BS EN 3. The contrasting panel — cream, black, blue or yellow — covers approximately 5% of the surface, near the label.

Is there a Class E fire in the UK?

No. Under BS EN 2, electrical is not a fire class. Extinguishers are tested and marked for use on live electrical equipment, but there is no “Class E” rating in current UK use.

What is Class L?

BS ISO 3941:2026 introduced Class L for lithium-ion battery fires. This describes the fuel hazard; it does not make an ordinary extinguisher suitable for battery thermal runaway. Assess the product’s specific test evidence and the premises’ emergency plan.

Does my workplace need every type of fire extinguisher?

No — it needs the types appropriate to the risks identified in your fire risk assessment. A typical office needs water or foam plus CO2. A commercial kitchen also needs wet chemical. A garage might need ABC powder. Your assessment specifies the mix.

How often should fire extinguishers be serviced?

For conventional units: at least monthly visual checks and annual basic servicing. Most water-based and powder units have a five-year extended service; CO2 has a ten-year overhaul. Some designs have different manufacturer-supported requirements. See our servicing guide.

What does a rating like “13A” or “55B” on a label mean?

The number expresses the size of fire the extinguisher has been tested to handle in a controlled fire-rating test. A 13A rating refers to a stack of timber of a specified size; 55B refers to a standardised tray test using 55 litres of liquid, comprising water and fuel. Larger numbers, larger fires.

Does my home need fire extinguishers?

Ordinary owner-occupied homes have no general requirement for portable extinguishers; rented or specialist accommodation may have additional requirements. Prioritise working alarms and a safe escape plan. In a fire, get out, stay out and call 999; seek fire-service advice before selecting equipment or attempting to use it.

Where to go from here

If you are working out what your premises need, start with a fire risk assessment — it is the document that drives every other choice. If you are training your team on fire safety basics, the foundation is our online fire safety awareness training course, which is RoSPA-approved, CPD-accredited, and designed for every employee in a UK workplace.

For deeper detail on a specific question, the spokes from this guide will take you there:

Sources & references

Official guidance and standards checked on 15 October 2026.

Train your whole team on fire safety basics with accredited online training.

Explore the Fire Safety Awareness Training course →
Mark McShane
Mark McShane
Health & Safety Training Specialist, Online CPD Academy

Mark writes about workplace health & safety, fire safety awareness and accredited online training for Fire Safety Awareness Training, part of Online CPD Academy.